Cancellation of Type Approval for Gas Extinguishing System Vessel Valves and Recall/Replacement of Release Devices

A release malfunction during low-temperature testing was confirmed for release device model HPR-510, resulting in cancellation of the type approval for the affected vessel valves and the designation of the affected release devices for recall and replacement. HPR-400/500 units shipped during the unfiled period had performance confirmed and may continue in use. Impact on installed products is currently unknown; however, a full recall and replacement will be implemented. Further developments will be disclosed as necessary.

Importance:
Page Updated: October 23, 2026
IR Disclosure Date: October 23, 2026

Key Figures

  • Affected vessel valve: Type approval cancelled for vessel valve NFCV-1, Approval No. Yo-092
  • Affected release device: Model HPR-510, Units shipped 4,001 units
  • Unfiled period: HPR-400 January 1999–April 2011, HPR-500 July 2008–February 2010, HPR-510 February 2011–September 2014

AI要約

Overview of the Incident

We discovered that there was an omission in the application for type approval of vessel valves used in our gas extinguishing systems and their associated release devices, and that some release devices were shipped during an unfiled period. Under supervision of the Safety Center, samples of vessel valves fitted with release devices from the unfiled period were collected and tested. As a result, we confirmed that vessel valves equipped with release device model HPR-510 exhibited insufficient gas release during low-temperature testing. Consequently, the type approval for the affected vessel valves has been cancelled, and the affected release devices are subject to recall and replacement.

Response and Impact

We will recall and replace all release devices shipped during the unfiled period. At present, the issue has not occurred in installed products, and we judge that continued use is possible provided operators observe precautions during manual operation until recall and replacement are completed. We will prioritize recall and replacement for installations in low-temperature environments and issue advisories. Performance confirmation was completed for HPR-400 and HPR-500 units shipped during the unfiled period, so installed units of those models may continue to be used.